AH5 00 Prog ram m ing M an ua l
Instruction code
PLF
Device
DX
DY
D
Symbol:
Explanation:
1.
When the conditional contact is switched from ON to OFF, the instruction PLF is executed, and
the device D sends out a pulse for a scan cycle.
2.
Please do not use the instruction PLS in the function block.
Example:
When X0.0 is ON, M0 is ON for a pulse time. When M0 is ON, Y0.0 is set to ON.
Timing chart:
X0 .0
One scan c ycle
M0
Y0 .0
5 - 1 8
Operand
D
X
Y
M
SM
D : Specified device
PLF
Function
Falling-edge output
S
T
C
HC
Bit
D
L
PR