5.2 Basic Instructions
Instruction code
LD/AND/OR
Device
DX
DY
S
Symbol:
Explanation:
1.
The instruction LD applies to contact A which starts from the mother line or contact A which is
the start of a contact circuit. It functions to reserve the current contents, and store the contact
state which is acquired in the accumulative register.
2.
The instruction AND is used to connect contact A in series. It functions to read the state of the
contact which is specified to be connected in series, and perform the AND operation with the
previous logical operation result. The final result is stored in the accumulative register.
3.
The instruction OR is used to connect contact A in parallel. It functions to read the state of the
contact which is specified to be connected in parallel, and perform the OR operation with the
previous logical operation result. The final result is stored in the accumulative register.
Example:
1.
Contact A of X0.0 is loaded, contact A of X0.1 is connected in series, contact A of X0.2 is
connected in parallel, and the coil Y0.0 is driven.
2.
When both X0.0 and X0.1 are ON, or when X0.2 is ON, Y0.0 is ON.
Operand
S
X
Y
M
SM
S : Specified device
LD
AND
OR
Ch ap te r 5 Bas ic Instruc ti ons
Function
Loading contact A/Connecting
contact A in series/Connecting
contact A in parallel
S
T
C
HC
Bit
D
L
PR
5 - 3