AH 5 00 Pr ogr am m ing Ma n ua l
10. The initial clock pulse
 SM404~SM410, and SR409~SR410
The PLC provides seven types of clock pulses. When the PLC is supplied with power, the
seven types of clock pulses act automatically. Users can set the interval of the clock pulse in
SM409 and SM410.
Device
10 millisecond clock pulse during which the pulse is ON for 5 milliseconds and is
SM404
OFF for 5 milliseconds
100 millisecond clock pulse during which the pulse is ON for 50 milliseconds
SM405
and is OFF for 50 milliseconds
200 millisecond clock pulse during which the pulse is ON for 100 milliseconds
SM406
and is OFF for 100 milliseconds
One second clock pulse during which the pulse is ON for 500 milliseconds and
SM407
is OFF for 500 milliseconds
Two second clock pulse during which the pulse is ON for one second and is
SM408
OFF for one second
2n second clock pulse during which the pulse is ON for n seconds and is OFF
for n seconds
SM409
The interval n is specified by SR409.
2n millisecond clock pulse during which the pulse is ON for n milliseconds and is
OFF for n milliseconds
SM410
The interval n is specified by SR410.
The clock pulses are illustrated as follows.
SM404 (10 ms)
SM405 (100 ms)
SM406 (200 ms)
SM407 (1 sec)
2 - 8 8
Function
10 ms
100 Hz
5 ms
100 ms
10 Hz
50 ms
200 ms
100 ms
1 sec
500 ms
5 Hz
1 Hz