Delta AH500 Programming Manual page 570

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

AH 5 00 Pr ogr am m ing Ma n ua l
The PLC sends the data.
Data
'0'
16#30
ADR 1
'1'
16#31
ADR 0
'1'
16#31
CMD 1
'0'
16#30
CMD 0
'2'
16#32
'0'
16#30
Data address
'0'
16#30
'0'
16#30
'0'
16#30
'0'
16#30
Data
'0'
16#30
'2'
16#32
'0'
16#30
Number of bytes
'4'
16#34
'0'
16#30
'0'
16#30
Data 1
'1'
16#31
'2'
16#32
'0'
16#30
'1'
16#31
Data 2
'F'
16#46
'4'
16#34
'C'
16#43
LRC CHK 1
'2'
16#32
LRC CHK 0
The PLC receives the data.
Data
'0'
16#30
ADR 1
'1'
16#31
ADR 0
'1'
16#31
CMD 1
'0'
16#30
CMD 0
'2'
16#32
'0'
16#30
Data address
'0'
16#30
'0'
16#30
'0'
16#30
'0'
16#30
Number of Registers
'0'
16#30
'2'
16#32
'C'
16#43
LRC CHK 1
'D'
16#44
LRC CHK 0
Additional remark:
1.
Please refer to the additional remark on the instruction RS for more information about the
related flags and the special registers.
2.
The instructions FWD, REV, STOP, RDST, and RSTEF can be used several times in the
program, but one instruction is executed at a time.
3.
If the value in S
exceeds the range, the instruction is not executed, SM0 is ON, and the error
1
code in SR0 is 16#2003.
6 - 4 0 2
Description
ADR (10) is the station address of the AC motor
drive.
CMD (10) is the command code.
16#12: The AC motor drive runs clockwise.
Operation frequency=K500Hz 16#01F4
LRC CHK (01) is the error checking code.
Description
ADR (10) is the station address of the AC motor
drive.
CMD (10) is the command code.

Advertisement

Table of Contents
loading