AH 5 00 Pr ogr am m ing Ma n ua l
API
Instruction code
0205
D
FINT
Device X
Y
M
S
D
Symbol:
Explanation:
1.
The double-precision floating-point number in the register specified by S is converted into the
binary integer. The binary floating-point number is rounded down to the nearest whole digit,
and becomes the bianry integer. The binary integer is stored in the register specified by D.
2.
The source device S used in the instruction FINT occupies four registers, and D used in FINT
occupies one register.
3.
The source device S used in the instruction DFINT occupies four registers, and D used in
DFINT occupies two registers.
4.
The operand D used in the instructions FINT and FLTP can not be the 32-bit counter.
5.
The instruction FINT is the opposite of the instruction FLTD.
6.
When the conversion result is zero, SM600 is ON.
7.
During the conversion, if the floating-point number is rounded down to the nearest whole digit,
SM601 will be ON.
8.
When the conversion result exceeds the range, SM602 is ON.
For the instruction FINT/FINTP, the range of conversion results is between -32,768 and
32,767.
For the instruction DFINT/DFINTP, the range of conversion results is between -2,147,483,648
and 2,147,483,647.
Example:
1. When X0.0 is ON, the double-precision floating-point number in (D3, D2, D1, D0) is converted
into the binary integer, and the conversion result is stored in D10. The binay floating-point
number is rounded down to the nearest whole digit.
2. When X0.1 is ON, the double-precision floating-point number in (D23, D22, D21, D20) is
converted into the binary integer, and the conversion result is stored in (D31, D30). The binay
floating-point number is rounded down to the nearest whole digit.
6 - 8 4
Operand
S, D
P
S
T
C
HC
D
Pulse instruction 32-bit instruction (5 steps) 64-bit instruction (5 steps)
AH500
S : Source device
D : Conversion result
Converting the 64-bit floating-point
number into the binary integer
L
SM SR
E
PR
AH500
Long word
Word/Double word
Function
K
16# "$"
DF
AH500