Issue 01/06
3.13

Parameter / command / drive data set

P0800[3]
BI: Download parameter set 0
CStat:
CT
P-Group: COMMANDS
Defines source of command to start download of parameter set 0 from attached AOP.
Index:
P0800[0] : 1st. Command data set (CDS)
P0800[1] : 2nd. Command data set (CDS)
P0800[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
Dependency:
1. The parameter set 0 can only be downloaded in conjunction with the AOP
2. Establish communications between the frequency inverter and AOP
3. The frequency inverter must be selected using the AOP if the AOP is connected at the COM link
interface (RS485)
4. Select the frequency inverter state "Ready" (r0002 = 1)
5. Signal from P0800:
0 = Do not download.
1 = Start to download parameter set 0 from the AOP.
BI: Dwnl .par.set 0
P0800.C
(0:0)
r0002 = 1
"Drive ready"
P0801[3]

BI: Download parameter set 1

CStat:
CT
P-Group: COMMANDS
Defines sources of command to start download of parameter set 1 from attached AOP.
Index:
P0801[0] : 1st. Command data set (CDS)
P0801[1] : 2nd. Command data set (CDS)
P0801[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
Note:
See parameter P0800
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U32
Active: first confirm
Inverter
&
BOP link
or
COM link
Transmission of "Parameter set 0" from AOP to inverter
Datatype: U32
Active: first confirm
Parameter Description
Min:
Unit: -
Def:
QuickComm.: No
Max:
AOP
Parameter set 0
Parameter set 1
. .
.
Parameter set 9
Min:
Unit: -
Def:
QuickComm.: No
Max:
Level
0:0
3
0:0
4000:0
Level
0:0
3
0:0
4000:0
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents