Mode Timer 1; Bo: Timer 1; Bo: Nout Timer 1; Bi: Timer 2 - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P2851

Mode timer 1

CStat:
CUT
P-Group: TECH
Selects mode of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.
Possible Settings:
0
ON delay (seconds)
1
OFF delay (seconds)
2
ON/OFF delay (seconds)
3
Pulse generator (seconds)
10
ON delay (minutes)
11
OFF delay (minutes)
12
ON/OFF delay (minutes)
13
Pulse generator (minutes)
Dependency:
P2802[0] is active level for the timer.
r2852

BO: Timer 1

P-Group: TECH
Displays output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.
Dependency:
P2802[0] is active level for the timer.
r2853

BO: Nout timer 1

P-Group: TECH
Displays Not-output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.
Dependency:
P2802[0] is active level for the timer.
P2854

BI: Timer 2

CStat:
CUT
P-Group: TECH
Define input signal of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.
Dependency:
P2802[1] is active level for the timer.
P2855
Delay time of timer 2
CStat:
CUT
P-Group: TECH
Defines delay time of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.
Dependency:
P2802[1] is active level for the timer.
P2856
Mode timer 2
CStat:
CUT
P-Group: TECH
Selects mode of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.
Possible Settings:
0
ON delay (seconds)
1
OFF delay (seconds)
2
ON/OFF delay (seconds)
3
Pulse generator (seconds)
10
ON delay (minutes)
11
OFF delay (minutes)
12
ON/OFF delay (minutes)
13
Pulse generator (minutes)
Dependency:
P2802[1] is active level for the timer.
r2857
BO: Timer 2
P-Group: TECH
Displays output of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.
Dependency:
P2802[1] is active level for the timer.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Datatype: U16
Unit: -
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: Float
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Parameter Description
Level
Min:
0
3
Def:
0
Max:
13
Level
Min:
-
3
Def:
-
Max:
-
Level
Min:
-
3
Def:
-
Max:
-
Level
Min:
0:0
3
Def:
0:0
Max:
4000:0
Level
Min:
0.0
3
Def:
0.0
Max:
9999.9
Level
Min:
0
3
Def:
0
Max:
13
Level
Min:
-
3
Def:
-
Max:
-
251