Fixed Pid Setpoint Mode - Bit 2; Fixed Pid Setpoint Mode - Bit 3; Bi: Fixed Pid Setp. Select Bit 0; Bi: Fixed Pid Setp. Select Bit 1 - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P2218[3]

Fixed PID setpoint mode - Bit 2

CStat:
CT
P-Group: TECH
BCD or direct selection Bit 2 for PID setpoint.
Possible Settings:
1
Direct selection
2
Direct selection + ON command
3
Binary coded selection + ON command
Index:
P2218[0] : 1st. Command data set (CDS)
P2218[1] : 2nd. Command data set (CDS)
P2218[2] : 3rd. Command data set (CDS)
P2219[3]

Fixed PID setpoint mode - Bit 3

CStat:
CT
P-Group: TECH
BCD or direct selection Bit 3 for PID setpoint.
Possible Settings:
1
Direct selection
2
Direct selection + ON command
3
Binary coded selection + ON command
Index:
P2219[0] : 1st. Command data set (CDS)
P2219[1] : 2nd. Command data set (CDS)
P2219[2] : 3rd. Command data set (CDS)
P2220[3]

BI: Fixed PID setp. select Bit 0

CStat:
CT
P-Group: COMMANDS
Defines command source of fixed PID setpoint selection Bit 0
Index:
P2220[0] : 1st. Command data set (CDS)
P2220[1] : 2nd. Command data set (CDS)
P2220[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
P2221[3]

BI: Fixed PID setp. select Bit 1

CStat:
CT
P-Group: COMMANDS
Defines command source of fixed PID setpoint selection Bit 1.
Index:
P2221[0] : 1st. Command data set (CDS)
P2221[1] : 2nd. Command data set (CDS)
P2221[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Parameter Description
Level
Min:
1
3
Def:
1
Max:
3
Level
Min:
1
3
Def:
1
Max:
3
Level
Min:
0:0
3
Def:
0:0
Max:
4000:0
Level
Min:
0:0
3
Def:
0:0
Max:
4000:0
227