Issue 01/06
P0708[3]

Function of digital input 8

CStat:
CT
P-Group: COMMANDS
Selects function of digital input 8 (via analog input)
Possible Settings:
0
Digital input disabled
1
ON/OFF1
2
ON reverse /OFF1
3
OFF2
- coast to standstill
4
OFF3
- quick ramp-down
9
Fault acknowledge
10
JOG right
11
JOG left
12
Reverse
13
MOP up (increase frequency)
14
MOP down (decrease frequency)
25
DC brake enable
29
External trip
33
Disable additional freq setpoint
99
Enable BICO parameterization
Index:
P0708[0] : 1st. Command data set (CDS)
P0708[1] : 2nd. Command data set (CDS)
P0708[2] : 3rd. Command data set (CDS)
Note:
Signals above 4 V are active, signals below 1,6 V are inactive.
Details:
See P0701 (function of digital input 1).
P0719[3]
Selection of cmd. & freq. setp.
CStat:
CT
P-Group: COMMANDS
Central switch to select control command source for inverter.
Switches command and setpoint source between freely programmable BICO parameters and fixed
command/setpoint profiles. Command and setpoint sources can be changed independently.
The tens digit chooses the command source and the units digit chooses the setpoint source.
Possible Settings:
0
Cmd = BICO parameter
1
Cmd = BICO parameter
2
Cmd = BICO parameter
3
Cmd = BICO parameter
4
Cmd = BICO parameter
5
Cmd = BICO parameter
6
Cmd = BICO parameter
7
Cmd = BICO parameter
10
Cmd = BOP
11
Cmd = BOP
12
Cmd = BOP
13
Cmd = BOP
15
Cmd = BOP
16
Cmd = BOP
17
Cmd = BOP
40
Cmd = USS on BOP link
41
Cmd = USS on BOP link
42
Cmd = USS on BOP link
43
Cmd = USS on BOP link
44
Cmd = USS on BOP link
45
Cmd = USS on BOP link
46
Cmd = USS on BOP link
47
Cmd = USS on BOP link
50
Cmd = USS on COM link
51
Cmd = USS on COM link
52
Cmd = USS on COM link
53
Cmd = USS on COM link
54
Cmd = USS on COM link
55
Cmd = USS on COM link
57
Cmd = USS on COM link
60
Cmd = CB on COM link
61
Cmd = CB on COM link
62
Cmd = CB on COM link
63
Cmd = CB on COM link
64
Cmd = CB on COM link
66
Cmd = CB on COM link
67
Cmd = CB on COM link
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Setpoint = BICO parameter
Setpoint = MOP setpoint
Setpoint = Analog setpoint
Setpoint = Fixed frequency
Setpoint = USS on BOP link
Setpoint = USS on COM link
Setpoint = CB on COM link
Setpoint = Analog 2 setp
Setpoint = BICO parameter
Setpoint = MOP setpoint
Setpoint = Analog setpoint
Setpoint = Fixed frequency
Setpoint = USS on COM link
Setpoint = CB on COM link
Setpoint = Analog 2 setp
Setpoint = BICO parameter
Setpoint = MOP setpoint
Setpoint = Analog setpoint
Setpoint = Fixed frequency
Setpoint = USS on BOP link
Setpoint = USS on COM link
Setpoint = CB on COM link
Setpoint = Analog 2 setp
Setpoint = BICO parameter
Setpoint = MOP setpoint
Setpoint = Analog setpoint
Setpoint = Fixed frequency
Setpoint = USS on BOP link
Setpoint = USS on COM link
Setpoint = Analog 2 setp
Setpoint = BICO parameter
Setpoint = MOP setpoint
Setpoint = Analog setpoint
Setpoint = Fixed frequency
Setpoint = USS on BOP link
Setpoint = CB on COM link
Setpoint = Analog 2 setp
Parameter Description
Level
Min:
0
2
Def:
0
Max:
99
Level
Min:
0
3
Def:
0
Max:
67