Parameter Description
P2179
Current limit for no load ident.
CStat:
CUT
P-Group: ALARMS
Threshold current for A0922 (load missing) in [%] relative to P0305 (rated motor current) as illustrated in the
diagram below.
Load missing
| I_act |
Pulse_enable
| V_act |
Note:
-
It may be that the motor is not connected (load missing) or a phase could be missing.
-
If a motor setpoint cannot be entered and the current limit (P2179) is not exceeded, Alarm A0922 (no
load applied) is issued when delay time (P2180) expires.
P2180
Delay time for load missing
CStat:
CUT
P-Group: ALARMS
Delay time to identify that the current is less than the threshold defined in P2179.
Details:
See diagram in P2179 (current limit for no load identification).
3.36
Load torque monitoring
P2181[3]
Belt failure detection mode
CStat:
CT
P-Group: ALARMS
Parameter P2181 activates or de-activates the load torque monitoring and defines the response to a load
torque fault.
Using the load torque monitoring, it is possible to detect a mechanical failure or an overload condition of the
mechanical transmission line, e.g. a broken drive belt or a stalled conveyor belt. In this case, the actual
torque/frequency actual value is compared to a programmed envelope characteristic (refer to P2182 -
P2190). If the actual torque/frequency actual value lies above or below the envelope curve, then after the
delay time P2192 expires, as a function of P2181, alarm A0952 is output or the drive inverter is tripped with
fault message F0452.
Possible Settings:
0
Belt failure detection disabled
1
Warning: Low torque / frequency
2
Warning: High torque / frequency
3
Warning: High / low torque / frequency
4
Trip: Low torque / frequency
5
Trip: High torque / frequency
6
Trip: High / low torque / frequency
Index:
P2181[0] : 1st. Command data set (CDS)
P2181[1] : 2nd. Command data set (CDS)
P2181[2] : 3rd. Command data set (CDS)
218
Datatype: Float
Unit: %
Active: Immediately
QuickComm.: No
1
0
Cur.lim:no-load ID
0.0 ... 10.0 [%]
P2179 (3.0)
1
0
0
Datatype: U16
Unit: ms
Active: Immediately
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Min:
0.0
Def:
3.0
Max:
10.0
Load missing
&
T 0
Load missing delay
0 ... 10000 [ms]
P2180 (2000)
Min:
0
Def:
2000
Max:
10000
Min:
0
Def:
0
Max:
6
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Issue 01/06
Level
3
r2197 Bit11
Level
3
Level
2