Value X1 Of Adc Scaling [V / Ma] - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
ADC1
OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA
ADC2
OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA
Possible Settings:
0
Unipolar voltage input (0 to +10 V)
1
Unipolar voltage input with monitoring (0 to 10 V)
2
Unipolar current input (0 to 20 mA)
3
Unipolar current input with monitoring (0 to 20 mA)
4
Bipolar voltage input (-10 V to +10 V)
Index:
P0756[0] : Analog input 1 (ADC 1)
P0756[1] : Analog input 2 (ADC 2)
Notice:
When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F0080) if
the analog input voltage falls below 50 % of the deadband voltage.
On account of h/w restirction it is not possible to select the bipolar voltage (see Enum declaration) for
analog input 2 (P0756[1] = 4).
Details:
See P0757 to P0760 (ADC scaling).
P0757[2]

Value x1 of ADC scaling [V / mA]

CStat:
CUT
P-Group: TERMINAL
Parameters P0757 - P0760 configure the input scaling as shown in the diagram:
P0756 = 0 ... 3, P0761 = 0
%
100 %
ASPmax
P0760
P0758
ASPmin
Where:
-
Analog setpoints represent a [%] of the normalized frequency in P2000.
-
Analog setpoints may be larger than 100 %.
-
ASPmax represents highest analog setpoint (this may be at 10 V or 20 mA).
-
ASPmin represents lowest analog setpoint (this may be at 0 V or 20 mA).
-
Default values provide a scaling of 0 V or 0 mA = 0 %, and 10 V or 20 mA = 100 %.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
1 2
3 4
Datatype: Float
Active: first confirm
4000 h
P0757
P0759
5 6 7 8 9
Unit: -
QuickComm.: No
V
mA
x
10 V
100%
20 mA
Parameter Description
Level
Min:
-20
2
Def:
0
Max:
20
89