Fixed frequencies

P1001[3]

Fixed frequency 1

CStat:
CUT
P-Group: SETPOINT
Defines fixed frequency setpoint 1.
There are three options available for selection of the fixed frequencies:
1. Direct selection
2. Direct selection + ON command
3. Binary coded selection + ON command
1. Direct selection (P0701 - P0706 = 15):
-
In this mode of operation 1 digital input selects 1 fixed frequency.
-
If several inputs are active together, the selected frequencies are summed.
-
E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
2. Direct selection + ON command (P0701 - P0706 = 16):
-
The fixed frequency selection combines the fixed frequencies with an ON command.
-
In this mode of operation 1 digital input selects 1 fixed frequency.
-
If several inputs are active together, the selected frequencies are summed.
-
E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
3. Binary coded selection + ON command (P0701 - P0706 = 17):
-
Up to 16 fixed frequencies can be selected using this method.
-
The fixed frequencies are selected according to the following table:
Index:
P1001[0] : 1st. Drive data set (DDS)
P1001[1] : 2nd. Drive data set (DDS)
P1001[2] : 3rd. Drive data set (DDS)
Example:
Binary coded selection :
0 Hz
FF0
P1001
FF1
P1002
FF2
P1003
FF3
P1004
FF4
P1005
FF5
P1006
FF6
P1007
FF7
P1008
FF8
P1009
FF9
P1010
FF10
P1011
FF11
P1012
FF12
P1013
FF13
P1014
FF14
P1015
FF15
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: Float
Active: Immediately
DIN4
DIN3
DIN2
0
0
0
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
1
0
0
1
0
1
1
0
1
1
1
0
1
1
0
1
1
1
1
1
1
Parameter Description
Min:
-650.00
Unit: Hz
Def:
0.00
QuickComm.: No
Max:
650.00
DIN1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Level
2
113