Bi: On Reverse/Off1; Bi: 1. Off2 - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P0842[3]

BI: ON reverse/OFF1

CStat:
CT
P-Group: COMMANDS
Allows ON/OFF1 reverse command source to be selected using BICO.
Normally in this case at a positive frequency setpoint, it is getting approached ccw (negative frequency
setpoint) The first three digits describe the parameter number of the command source and the last digit
denotes the bit setting for that parameter.
Index:
P0842[0] : 1st. Command data set (CDS)
P0842[1] : 2nd. Command data set (CDS)
P0842[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.0
= ON/OFF1 via BOP
Details:
See parameter P0840.
P0844[3]

BI: 1. OFF2

CStat:
CT
P-Group: COMMANDS
Defines first source of OFF2.
The first three digits describe the parameter number of the command source and the last digit denotes the
bit setting for that parameter. If one of the digital inputs is selected for OFF2, the inverter will not run unless
the digital input is active.
f
act
P1082
f
max
r0052 Bit02
Operation
Pulse
cancellation
Index:
P0844[0] : 1st. Command data set (CDS)
P0844[1] : 2nd. Command data set (CDS)
P0844[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.0
= ON/OFF1 via BOP
19.1
= OFF2: Electrical stop via BOP
Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).
Note:
-
OFF2 means an immediate pulse inhibit; the motor coasts down.
-
OFF2 is low active.
-
The following applies for the priority of all of the OFF commands: OFF2, OFF3, OFF1
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
OFF2
f
act,motor
t
f
act,inverter
t
Parameter Description
Level
Min:
0:0
3
Def:
0:0
Max:
4000:0
Level
Min:
0:0
3
Def:
1:0
Max:
4000:0
103