Belt Threshold Frequency 1; Belt Threshold Frequency 2 - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P2182[3]

Belt threshold frequency 1

CStat:
CUT
P-Group: ALARMS
Sets a frequency threshold 1 for comparing actual torque to torque the envelope for belt failure detection.
The frequency torque envelope is defined by 9 parameters - 3 are frequency parameters (P2182 - P2184),
and the other 6 define the low and high torque limits (P2185 - P2190) for each frequency (see diagram
below).
P2189
Upper torque threshold 3
P2190
Lower torque threshold 3
P2187
Upper torque threshold 2
P2188
Lower torque threshold 2
P2185
Upper torque threshold 1
P2186
Lower torque threshold 1
The allowed frequency/torque region is defined by the shaded area. When the torque falls outside the area
shown, a trip or warning occurs (see parameter P2181).
Index:
P2182[0] : 1st. Drive data set (DDS)
P2182[1] : 2nd. Drive data set (DDS)
P2182[2] : 3rd. Drive data set (DDS)
Note:
-
The load torque monitoring function is not active below the frequency defined in P2182 and above the
frequency defined in P2184.
-
The current and torque limits of the drive inverter and motor still apply over the complete frequency
range.
-
The drive inverter output frequency is defined using Parameter P1080 and P1082. These limits should
be carefully observed for the load torque monitoring frequencies.
P2183[3]

Belt threshold frequency 2

CStat:
CUT
P-Group: ALARMS
Sets a threshold F2 for comparing actual torque to torque the envelope for belt failure detection.
Index:
P2183[0] : 1st. Drive data set (DDS)
P2183[1] : 2nd. Drive data set (DDS)
P2183[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: Float
Active: Immediately
|Torque| [Nm]
P1080
Min. frequency
P2182
Threshold frequency 2
Threshold frequency 1
Boundary zones
De-activated monitoring
Datatype: Float
Active: Immediately
Parameter Description
Min:
Unit: Hz
Def:
QuickComm.: No
Max:
P1082
Max. frequency
|Frequency|
P2183
P2184
Threshold frequency 3
Envelope curve
Active monitoring
Min:
Unit: Hz
Def:
QuickComm.: No
Max:
Level
0.00
3
5.00
650.00
[Hz]
Level
0.00
2
30.00
650.00
219