Parameter Description
r2018[8]

CO: PZD from COM link (USS)

P-Group: COMM
Displays process data received via USS on COM link.
PZD4
STW2
PZD
BCC
Process data
Index:
r2018[0] : Received word 0
r2018[1] : Received word 1
r2018[2] : Received word 2
r2018[3] : Received word 3
r2018[4] : Received word 4
r2018[5] : Received word 5
r2018[6] : Received word 6
r2018[7] : Received word 7
Note:
The control words can be viewed as bit parameters r2036 and r2037.
Restrictions:
-
If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.
-
If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the
2nd PZD-word,
-
When P2012 is greater than or equal to 4 the additional control word (2nd control word) must
transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).
200
Datatype: U16
PZD3
PZD2
PZD1
HSW
STW1
P2012
PKW
ADR
LGE
Parameter
USS telegram
USS on COM link
Min:
-
Unit: -
Def:
-
Max:
-
r2018
[0]
[1]
[2]
[3]
.
.
.
[7]
STX
Start of text
LGE
Length
ADR
Address
PKW
Parameter ID value
PZD
Process data
STX
BCC
Block check character
STW
Control word
HSW
Main setpoint
PZD mapping to parameter r 2 018
MICROMASTER 440
6SE6400-5BB00-0BP0
Issue 01/06
Level
3
r2036
r2037
Parameter List