Bi: Function Of Digital Output 2; Bi: Function Of Digital Output 3 - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P0732[3]

BI: Function of digital output 2

CStat:
CUT
P-Group: COMMANDS
Defines source of digital output 2.
Index:
P0732[0] : 1st. Command data set (CDS)
P0732[1] : 2nd. Command data set (CDS)
P0732[2] : 3rd. Command data set (CDS)
Common Settings:
52.0
Drive ready
52.1
Drive ready to run
52.2
Drive running
52.3
Drive fault active
52.4
OFF2 active
52.5
OFF3 active
52.6
Switch on inhibit active
52.7
Drive warning active
52.8
Deviation setpoint/actual value
52.9
PZD control (Process Data Control)
52.A
Maximum frequency reached
52.B
Warning: Motor current limit
52.C
Motor holding brake (MHB) active
52.D
Motor overload
52.E
Motor running direction right
52.F
Inverter overload
53.0
DC brake active
53.1
Act. freq. f_act > P2167 (f_off)
53.2
Act. freq. f_act <= P1080 (f_min)
53.3
Act. current r0027 > P2170
53.4
Act. freq. f_act > P2155 (f_1)
53.5
Act. freq. f_act <= P2155 (f_1)
53.6
Act. freq. f_act >= setpoint
53.7
Act. Vdc r0026 < P2172
53.8
Act. Vdc r0026 > P2172
53.A
PID output r2294 == P2292 (PID_min)
53.B
PID output r2294 == P2291 (PID_max) 0 Closed
P0733[3]

BI: Function of digital output 3

CStat:
CUT
P-Group: COMMANDS
Defines source of digital output 3.
Index:
P0733[0] : 1st. Command data set (CDS)
P0733[1] : 2nd. Command data set (CDS)
P0733[2] : 3rd. Command data set (CDS)
Common Settings:
52.0
Drive ready
52.1
Drive ready to run
52.2
Drive running
52.3
Drive fault active
52.4
OFF2 active
52.5
OFF3 active
52.6
Switch on inhibit active
52.7
Drive warning active
52.8
Deviation setpoint/actual value
52.9
PZD control (Process Data Control)
52.A
Maximum frequency reached
52.B
Warning: Motor current limit
52.C
Motor holding brake (MHB) active
52.D
Motor overload
52.E
Motor running direction right
52.F
Inverter overload
53.0
DC brake active
53.1
Act. freq. f_act > P2167 (f_off)
53.2
Act. freq. f_act <= P1080 (f_min)
53.3
Act. current r0027 > P2170
53.4
Act. freq. f_act > P2155 (f_1)
53.5
Act. freq. f_act <= P2155 (f_1)
53.6
Act. freq. f_act >= setpoint
53.7
Act. Vdc r0026 < P2172
53.8
Act. Vdc r0026 > P2172
53.A
PID output r2294 == P2292 (PID_min)
53.B
PID output r2294 == P2291 (PID_max) 0 Closed
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
0 Closed
0 Closed
0 Closed
0 Closed
1 Closed
1 Closed
0 Closed
0 Closed
1 Closed
0 Closed
0 Closed
1 Closed
0 Closed
1 Closed
0 Closed
1 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
0 Closed
0 Closed
0 Closed
0 Closed
1 Closed
1 Closed
0 Closed
0 Closed
1 Closed
0 Closed
0 Closed
1 Closed
0 Closed
1 Closed
0 Closed
1 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
Parameter Description
Level
Min:
0:0
2
Def:
52:7
Max:
4000:0
Level
Min:
0:0
2
Def:
0:0
Max:
4000:0
85