Issue 01/06
r0752[2]

Act. input of ADC [V] or [mA]

P-Group: TERMINAL
Displays smoothed analog input value in volts before the characteristic block.
ADC channel
DIP switch
KL3
ADC
ADC+
KL 4
type
ADC−
Index:
r0752[0] : Analog input 1 (ADC 1)
r0752[1] : Analog input 2 (ADC 2)
P0753[2]

Smooth time ADC

CStat:
CUT
P-Group: TERMINAL
Defines filter time (PT1 filter) in [ms] for analog input.
Index:
P0753[0] : Analog input 1 (ADC 1)
P0753[1] : Analog input 2 (ADC 2)
Note:
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
P0753 = 0 : No filtering
r0754[2]

Act. ADC value after scaling [%]

P-Group: TERMINAL
Shows smoothed value of analog input in [%] after scaling block.
Index:
r0754[0] : Analog input 1 (ADC 1)
r0754[1] : Analog input 2 (ADC 2)
Dependency:
P0757 to P0760 define range (ADC scaling).
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: Float
P0756
P0753
A
ADC
type
D
1.7 V
1
0
3 .9 V
Datatype: U16
Active: first confirm
Datatype: Float
Parameter Description
Min:
Unit: -
Def:
Max:
r0754
P1000
P0761
ADC
ADC
dead
r0755
scaling
zone
P0762
P0756
P0761
T
0
Wire
breakage
sensing
r0722
r0722.6
P0707
Min:
Unit: ms
Def:
QuickComm.: No
Max:
Min:
Unit: %
Def:
Max:
Level
-
2
-
-
Setpoint
Pxxxx
r0752
F0080
r0751
Pxxxx
Function
Level
0
3
3
10000
Level
-
2
-
-
87