P1076[3]

CI: Additional setpoint scaling

CStat:
CT
P-Group: SETPOINT
Defines source of scaling for additional setpoint (to be added to main setpoint).
Index:
P1076[0] : 1st. Command data set (CDS)
P1076[1] : 2nd. Command data set (CDS)
P1076[2] : 3rd. Command data set (CDS)
Common Settings:
1
= Scaling of 1.0 (100%)
755
= Analog input 1 Setpoint
1024
= Fixed Frequency Setpoint
1050
= MOP Setpoint
r1078

CO: Total frequency setpoint

P-Group: SETPOINT
Displays sum of main and additional setpoints in [Hz].
r1079

CO: Selected frequency setpoint

P-Group: SETPOINT
Displays selected frequency setpoint.
Following frequency setpoints are displayed:
-
r1078 Total frequency setpoint
-
P1058 JOG frequency right
-
P1059 JOG frequency left
Dependency:
P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG
left respectively.
Note:
P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.
126
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: Float
Unit: Hz
Datatype: Float
Unit: Hz
Issue 01/06
Min:
0:0
Def:
1:0
Max:
4000:0
Min:
-
Def:
-
Max:
-
Min:
-
Def:
-
Max:
-
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Level
3
Level
3
Level
3