P2257

Ramp-up time for PID setpoint

CStat:
CUT
P-Group: TECH
Sets the ramp-up time for the PID setpoint.
PID Setpoint (%)
100 %
x
2
x
1
0
Dependency:
P2200 = 1 (PID control is enabled) disables normal ramp-up time (P1120).
PID ramp time effective only on PID setpoint and only active
-
when PID setpoint is changed or
-
when RUN command is given.
Notice:
Setting the ramp-up time too short may cause the inverter to trip, on overcurrent for example.
P2258

Ramp-down time for PID setpoint

CStat:
CUT
P-Group: TECH
Sets ramp-down time for PID setpoint.
PID Setpoint (%)
100 %
x
2
x
1
0
Dependency:
-
P2200 = 1 (PID control is enabled) disables normal ramp-up time (P1120).
-
PID setpoint ramp effective only on PID setpoint changes.
-
P1121 (ramp-down time) and P1135 (OFF3 ramp-down time) define the ramp times used after OFF1
and OFF3 respectively.
Notice:
Setting the ramp-down time too short can cause the inverter to trip on overvoltage (F0002) / overcurrent
(F0001).
r2260

CO: PID setpoint after PID-RFG

P-Group: TECH
Displays total active PID setpoint after PID-RFG in [%].
Note:
r2260 = 100 % corresponds to 4000 hex
234
Datatype: Float
Active: Immediately
t
12
P2257
Datatype: Float
Active: Immediately
t
21
P2258
Datatype: Float
Min:
0.00
Unit: s
Def:
1.00
QuickComm.: No
Max:
650.00
t (s)
x
x
2
1
=
t
12
100
%
Min:
0.00
Unit: s
Def:
1.00
QuickComm.: No
Max:
650.00
t (s)
x
x
1
2
=
t
21
100
%
Min:
-
Unit: %
Def:
-
Max:
-
MICROMASTER 440
6SE6400-5BB00-0BP0
Issue 01/06
Level
2
P2257
Level
2
P2258
Level
2
Parameter List