Issue 01/06
3.29

Control mode

P1300[3]
Control mode
CStat:
CT
P-Group: CONTROL
Controls relationship between speed of motor and voltage supplied by inverter as illustrated in the diagram
below.
V
V
n
P1300 = 0
0
Possible Settings:
0
V/f with linear characteristic
1
V/f with FCC
2
V/f with parabolic characteristic
3
V/f with programmable characteristic
4
Reserved
5
V/f for textile applications
6
V/f with FCC for textile applications
19
V/f control with independent voltage setpoint
20
Sensorless vector control
21
Vector control with sensor
22
Sensorless vector torque-control
23
Vector torque-control with sensor
Index:
P1300[0] : 1st. Drive data set (DDS)
P1300[1] : 2nd. Drive data set (DDS)
P1300[2] : 3rd. Drive data set (DDS)
Dependency:
See parameter P0205, P0500
Caution:
When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f
mode (see P1300) first. Run the drive and compare r0061 with r0021 that should agree in
-
sign and
-
magnitude (with a deviation of only a few percent).
Only if both criteria are fullfilled, change P1300 and select VC (P1300 = 21 or 23).
P0400 = 1 (single channel encoder) will only allow operation in one direction. If operation in both directions
is required, connect an encoder with 2 channels (A and B) and select setting 2. See the Operating
Instructions of the encoder module for more information.
Note:
P1300 = 1 : V/f with FCC (flux current control)
-
Maintains motor flux current for improved efficiency.
-
If FCC is chosen, linear V/f is active at low frequencies.
P1300 = 2 : V/f with a quadratic characteristic
-
Suitable for centrifugal fans / pumps
P1300 = 3 : V/f with a programmable characteristic
-
User defined characteristic (see P1320)
-
For synchronous motors (e.g. SIEMOSYN motors)
P1300 = 5,6 : V/f for textil applications
-
Slip compensation disabled.
-
Imax controller modifies the output voltage only.
-
Imax controller does not influence the output frequency.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Active: first confirm
V
V
max
r0071
V
n
P0304
P1325
P1323
P1321
P1310
P1300 = 2
f
f
n
0 Hz
Parameter Description
Min:
Unit: -
Def:
QuickComm.: Yes
Max:
P1300 = 3
f0
f1
f2
f3
P1320
P1322
P1324
Level
0
2
0
23
f
f
f
n
max
P0310
P1082
153