Faults and Alarms

F0054 Incorrect I/O module

Quit
Refer to F0001
Cause
-
incorrect I/O module inserted.
-
no ID of the I/O module found, no data.
Diagnosis & Remedy
Please check the following:
-
check I/O data, if required repeat the operation
-
the installation of the I/O module in the inverter if required, replace the I/O module

F0060 Asic time slice overflow

Quit
Refer to F0001
Cause
-
internal communications failure/error
Diagnosis & Remedy
-
if the error still occurs, replace the inverter.
-
contact customer service!

F0070 CB setpoint fault

Quit
Refer to F0001
Cause
-
no setpoints received via the communications bus during the telegram failure time.
Diagnosis & Remedy
-
check the communications module (CB) and communications partner.

F0071 USS(BOP link) setpoint fault

Quit
Refer to F0001
Cause
-
no setpoint was received via the USS during the telegram off time
Diagnosis & Remedy
-
check USS master
F0072 USS(COMM link) setpoint fault
Quit
Refer to F0001
Cause
-
no setpoints received via the USS during the telegram off time
Diagnosis & Remedy
-
check USS master
F0080 ADC input signal lost
Quit
Refer to F0001
Cause
-
wire breakage
-
signal outside the limit values
F0085 External fault
Quit
Refer to F0001
Cause
-
external fault as a result of command input via terminals.
Diagnosis & Remedy
-
inhibit terminal input to initiate fault.