Issue 01/06
3.40

Inverter parameters

P3900
End of quick commissioning
CStat:
C
P-Group: QUICK
Performs calculations necessary for optimized motor operation.
After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically
reset to their original value 0.
Possible Settings:
0
No quick commissioning
1
Start quick commissioning with factory reset
2
Start quick commissioning
3
Start quick commissioning only for motor data
Dependency:
Changeable only when P0010 = 1 (quick commissioning)
Note:
P3900 = 1 :
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick
commissioning", are retained; all other parameter changes, including the I/O settings, are lost. Motor
calculations are also performed.
P3900 = 2 :
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning
menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the
motor calculations performed.
P3900 = 3 :
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick
commissioning with this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values (see parameter P0340, setting P0340
= 1).
P3950
Access of hidden parameters
CStat:
CUT
P-Group: ALWAYS
Accesses special parameters for development (expert only) and factory functionality (calibration parameter).
r3954[13]
CM version and GUI ID
P-Group: -
Used to classify firmware (only for SIEMENS internal purposes).
Index:
r3954[0] : CM version (major release)
r3954[1] : CM version (minor release)
r3954[2] : CM version (baselevel or patch)
r3954[3] : GUI ID
r3954[4] : GUI ID
r3954[5] : GUI ID
r3954[6] : GUI ID
r3954[7] : GUI ID
r3954[8] : GUI ID
r3954[9] : GUI ID
r3954[10] : GUI ID
r3954[11] : GUI ID major release
r3954[12] : GUI ID minor release
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: Yes
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Parameter Description
Level
Min:
0
1
Def:
0
Max:
3
Level
Min:
0
4
Def:
0
Max:
255
Level
Min:
-
4
Def:
-
Max:
-
257