Gain Speed Controller (Slvc); Integral Time N-Ctrl. (Slvc); Bi: Set Integrator Of N-Ctrl.; Ci: Set Integrator Value N-Ctrl. - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P1470[3]

Gain speed controller (SLVC)

CStat:
CUT
P-Group: CONTROL
Enters gain of speed controller for sensorless vector control (SLVC).
P1492
r1170
Freq. setpoint
Act. frequency
from observer model
Index:
P1470[0] : 1st. Drive data set (DDS)
P1470[1] : 2nd. Drive data set (DDS)
P1470[2] : 3rd. Drive data set (DDS)
P1472[3]

Integral time n-ctrl. (SLVC)

CStat:
CUT
P-Group: CONTROL
Enters integral time of speed controller for sensorless vector control (SLVC).
Index:
P1472[0] : 1st. Drive data set (DDS)
P1472[1] : 2nd. Drive data set (DDS)
P1472[2] : 3rd. Drive data set (DDS)
P1477[3]

BI: Set integrator of n-ctrl.

CStat:
CUT
P-Group: CONTROL
Selects source to read in command to enable speed controller.
Index:
P1477[0] : 1st. Command data set (CDS)
P1477[1] : 2nd. Command data set (CDS)
P1477[2] : 3rd. Command data set (CDS)
P1478[3]

CI: Set integrator value n-ctrl.

CStat:
UT
P-Group: CONTROL
Selects source for integral part of speed controller.
Index:
P1478[0] : 1st. Command data set (CDS)
P1478[1] : 2nd. Command data set (CDS)
P1478[2] : 3rd. Command data set (CDS)
Dependency:
In case of sensorless vector control, integrator freezing must be selected (Bit 1 "Integral freeze (SLVC)" of
P1400 has to be set) to save the integrator output.
Note:
-
If the setting command is not connected (P1477=0), a pending value is read in after pulse enable at the
end of the excitation time (P0346) and the integral component of the speed controller is set once.
-
If the P1482 (integral component of speed controller) is connected upon pulse enable, the integral
component of the controller is set to the last value prior the pulse inhibit.
-
Neither function works after flying start.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: Float
Active: Immediately
150 ms
r1490
Precontrol
r1084
r1438
*)
r0063
Datatype: U16
Active: Immediately
Datatype: U32
Active: first confirm
Datatype: U32
Active: first confirm
Parameter Description
Min:
Unit: -
Def:
QuickComm.: No
Max:
Droop
r1518
Kp
Tn
r0064
r1508
*) only active , if pre-control is enabled
(P1496 > 0)
Min:
Unit: ms
Def:
QuickComm.: No
Max:
Min:
Unit: -
Def:
QuickComm.: No
Max:
Min:
Unit: -
Def:
QuickComm.: No
Max:
Level
0.0
2
3.0
2000.0
Torque
setpoint
r0079
Level
25
2
400
32001
Level
0:0
3
0:0
4000:0
Level
0:0
3
0:0
4000:0
169