Flux Control; Co: Fixed Value Flux Setpoint; Co: Upper Torque Limit (Total); Co: Lower Torque Limit (Total) - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
r1538

CO: Upper torque limit (total)

P-Group: CONTROL
Displays total upper torque limitation.
Torque limitation :
CO: Upper trq. lim
P1520
CO: Lower trq. lim
P1521
CI: Add. trq. setp
P1511.C
(0:0)
Speed controller
or
Torque controller
r1539

CO: Lower torque limit (total)

P-Group: CONTROL
Displays total lower torque limitation.
Details:
See parameter r1538.
3.29.2.7

Flux control

P1570[3]

CO: Fixed value flux setpoint

CStat:
CUT
P-Group: CONTROL
Parameter to set the flux setpoint as a % relative to the rated motor flux.
Index:
P1570[0] : 1st. Drive data set (DDS)
P1570[1] : 2nd. Drive data set (DDS)
P1570[2] : 3rd. Drive data set (DDS)
Note:
-
In the base speed range, the flux setpoint P1570 is converted into the field-generating current
component isd (P1570 = 100% corresponds to r0331).
-
For values below 100%, the drive is under-magnetized and above this, is over-magnetized.
-
If P1570 is set to more than 100%, then the flux setpoint, depending on the load, is increased from
100% (under no-load conditions) to this value (under rated load, refer to the diagram).
-
If in so doing, the maximum drive inverter output voltage is reached, the rotor flux is reduced in order to
keep the output voltage constant (or the EMF) with increasing speed.
-
The maximum possible output voltage r0071 of the drive inverter is determined by the DC link voltage
r0026 and the maximum modulation depth P1803 in the gating unit.
Ψ
set
P1570
Ψ
N
(100 %)
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: Float
CO: Upper trq. lim [Nm]
CI: Upper trq. lim
r1526
P1522.C
(1520:0)
CO: Lower trq. lim [Nm]
CI: Lower trq. lim
r1527
P1523.C
(1521:0)
P1525
Scal. low trq . lim
P0640
Motor ovl fact [%]
P0305
Rated mot. current
Datatype: Float
Datatype: Float
Active: Immediately
Ψ
i
Motor
i
N,Motor
Parameter Description
Min:
Unit: Nm
Def:
Max:
P1530
P1531
Motoring power lim
Regener. power lim
Torque limitation
r0067
CO: Outp cur limit [A]
Motor / inverter
protection
Max. inverter cur [A]
r0209
Min:
Unit: Nm
Def:
Max:
Min:
Unit: %
Def:
QuickComm.: No
Max:
i
Motor
i
N,Motor
Field weakening
Level
-
2
-
-
CO:Total up TrqLim [Nm]
r1538
CO:Total lw TrqLim [Nm]
r1539
CO: Total trq setp [Nm]
r0079
Current
controller
Level
-
2
-
-
Level
50.0
2
107.0
200.0
f
179