Parameter Description
It is recommended to modify P0205 first. Afterwards motor parameter may be adapted. Motor parameter will
be overridden by changing this sequence.
P0205
Notice:
-
The parameter value is not reset by the factory setting (see P0970).
-
To set P0205 = 1 (variable torque) is not possible for all inverters.
-
Use setting 1 (variable torque) only for variable-torque applications (e.g. pumps and fans). If used for
constant-load applications, I2t warning will be produced too late, causing overheating in the motor.
r0206

Rated inverter power [kW] / [hp]

P-Group: INVERTER
Displays nominal rated motor power from inverter.
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
=
r0206
[hp]
0.75
r0207[3]

Rated inverter current

P-Group: INVERTER
Indicates the rated inverter current.
Index:
r0207[0] : Rated inverter current
r0207[1] : Rated VT current
r0207[2] : Rated CT current
Note:
VT (variable torque) and CT (constant torque) specify the overload capability (CT/VT application) of the
inverter. The definition of the rated as well as the overload and base load values depend on the inverter
type and inverter power. The different values can be taken from the appropriate Catalog or are saved in the
drive inverter (refer to Fig.).
The VT rated current r0207[1] or CT rated current r0207[2] represent the matching 4-pole Siemens IEC
standard motor for the selected load duty cycle (refer to the diagram). Parameters r0207[1] or r0207[2] are
used as default values for P0305 as a function of the CT/VT application (load duty cycle). If r0207[1] =
r0207[2], then it is not possible to make a differentiation between a CT/VT application.
Overload in operation is only possible if, before the overload condition, the load current was less than the
rated current. For drives, which must be able to handle overload conditions, it is first necessary to define a
base load current for the required load.
If the full overload capability is used, then this is detected using an I²t monitoring and the power module is
protected as a function of parameter P0290.
r0208

Rated inverter voltage

P-Group: INVERTER
Displays nominal AC supply voltage of inverter.
Value:
r0208 = 230 : 200 - 240 V +/- 10 %
r0208 = 400 : 380 - 480 V +/- 10 %
r0208 = 575 : 500 - 600 V +/- 10 %
46
Inverter parameters
r0207 I
I, n
r0208 P
I, n
r0209 I
I, max
Motor parameters
P0305 I
M,n
P0307 P
M,n
P0640 I
M,max
Technology parameter
P0500
Datatype: Float
r0206
[kW ]
Datatype: Float
Datatype: U32
User
Control parameter
P0500
P1300
Min:
Unit: -
Def:
Max:
Min:
Unit: A
Def:
Max:
Min:
Unit: V
Def:
Max:
MICROMASTER 440
Issue 01/06
P1300
Level
-
2
-
-
Level
-
2
-
-
Level
-
2
-
-
Parameter List
6SE6400-5BB00-0BP0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents