Parameter Description
P2849

BI: Timer 1

CStat:
CUT
P-Group: TECH
Define input signal of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.
P2849
Index0
In
Out
P2851 = 0 (ON Delay)
P2851 = 1 (OFF Delay)
P2851 = 2 (ON-OFF Delay)
P2851 = 3 (Pulse Generator)
In
Out
In
Out
Dependency:
P2802[0] is active level for the timer.
P2850

Delay time of timer 1

CStat:
CUT
P-Group: TECH
Defines delay time of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.
Dependency:
P2802[0] is active level for the timer.
250
Datatype: U32
Active: first confirm
P2850 (0.000)
P2851(0)
P2800 P2802.0
Delay Time
Mode
ON Delay
0
T
0
OFF Delay
1
0
T
I
n
ON/OFF Delay
2
T
T
Pulse Gernerator
3
T
P2850
P2850
P2850
P2850
Datatype: Float
Active: first confirm
Min:
0:0
Unit: -
Def:
0:0
QuickComm.: No
Max:
4000:0
Ou
t
r2852
NOu
t
r2853
1
P2850
P2850
Min:
0.0
Unit: -
Def:
0.0
QuickComm.: No
Max:
9999.9
MICROMASTER 440
6SE6400-5BB00-0BP0
Issue 01/06
Level
3
t
t
t
t
t
t
t
t
Level
3
Parameter List