Free function blocks (FFB)

P2800

Enable FFBs

CStat:
CUT
P-Group: TECH
Free function blocks (FFB) are enabled in two steps.
1. Parameter P2800 enables all free function blocks , normally (P2800 = 1).
2. Parameters P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0
oder P2802[x] > 0).
Possible Settings:
0
Disabled
1
Enabled
Dependency:
All active function blocks will be calculated in every 132 ms.
P2801[17] Activate FFBs
CStat:
CUT
P-Group: TECH
Free function blocks (FFB) are enabled in two steps.
1. Parameter P2800 enables all free function blocks , normally (P2800 = 1)
2. Parameters P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0
oder P2802[x] > 0)
In addition, Parameters P2801 and P2802 determine the chronological order of each function block. The
following table shows that the priority increases from left to right and from bottom to top.
Level
3
Level
2
Level
1
0
Inactive
Possible Settings:
0
Not Active
1
Level 1
2
Level 2
3
Level 3
Index:
P2801[0] : Enable AND 1
P2801[1] : Enable AND 2
P2801[2] : Enable AND 3
P2801[3] : Enable OR 1
P2801[4] : Enable OR 2
P2801[5] : Enable OR 3
P2801[6] : Enable XOR 1
P2801[7] : Enable XOR 2
P2801[8] : Enable XOR 3
P2801[9] : Enable NOT 1
P2801[10] : Enable NOT 2
P2801[11] : Enable NOT 3
P2801[12] : Enable D-FF 1
P2801[13] : Enable D-FF 2
P2801[14] : Enable RS-FF 1
P2801[15] : Enable RS-FF 2
P2801[16] : Enable RS-FF 3
Example:
P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2
FFBs will be calculated in following order:
P2802[3], P2801[3] , P2801[4], P2802[4]
Dependency:
-
Set P2800 to 1 to enable function blocks.
-
All active function blocks will be calculated in every 132 ms.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Parameter Description
Level
Min:
0
3
Def:
0
Max:
1
Level
Min:
0
3
Def:
0
Max:
3
Priority 2
low
high
241