Issue 01/06
P0292

Inverter temperature warning

CStat:
CUT
P-Group: INVERTER
Defines the temperature difference (in ºC) between the Overtemperature trip threshold and the warning
threshold of the inverter. The trip threshold is stored internally by the inverter and cannot be changed by the
user.
Temperature warning threshold of inverter T _warn
T
= T
warn
Temperature shutdown threshold of inverter T _trip
Temperature
Heat sink
IGBT
Input rectifier
Cooling air
Control board
If the actual inverter temperature (r0037) exceeds the corresponding threshold, a warning A0504, if the
temperature still increases then a fault F0004 will be displayed.
P0294

Inverter I2t overload warning

CStat:
CUT
P-Group: INVERTER
Defines the [%] value at which alarm A0505 (inverter I2t) is generated.
Inverter I2t calculation is used to determine a maximum tolerable period for inverter overload. The I2t
calculation value is deemed = 100 % when this maximum tolerable period is reached.
Dependency:
That the output current of the inverter has been reduced and that the value of I2t does not exceed 100%.
Note:
P0294 = 100 % corresponds to stationary nominal load.
P0295

Inverter fan off delay time

CStat:
CUT
P-Group: TERMINAL
Defines inverter fan switch off delay time in seconds after drive has stopped.
Note:
Setting to 0, inverter fan will switch off when the drive stops, that is no delay.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Active: first confirm
- P0292
trip
A - C
D - F
110 °C
95 °C
140 °C
145 °C
-
-
-
-
-
-
Datatype: Float
Active: first confirm
Datatype: U16
Active: first confirm
Parameter Description
Min:
Unit: °C
Def:
QuickComm.: No
Max:
MM440, Frame Size
F
FX
95 kW
110 kW
132 kW
600 V
CT
CT
CT
80 °C
88 °C
91 °C
80 °C
145 °C
150 °C
150 °C
145 °C
-
75 °C
75 °C
75 °C
-
55 °C
55 °C
55 °C
-
65 °C
65 °C
65 °C
Min:
Unit: %
Def:
QuickComm.: No
Max:
Min:
Unit: s
Def:
QuickComm.: No
Max:
Level
0
3
5
25
GX
160 kW
200 kW
CT
CT
82 °C
88 °C
147 °C
150 °C
75 °C
75 °C
55 °C
50 °C
65 °C
65 °C
Level
10.0
4
95.0
100.0
Level
0
3
0
3600
49