Threshold Dc-Link Voltage; Delay Time Dc-Link Voltage - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Parameter Description
P2172[3]

Threshold DC-link voltage

CStat:
CUT
P-Group: ALARMS
Defines DC link voltage to be compared to actual voltage as illustrated in the diagram below.
V
dc
P2172
V
< P2172
dc_act
1
r0053
Bit07
0
V
> P2172
dc_act
1
r0053
Bit08
0
Index:
P2172[0] : 1st. Drive data set (DDS)
P2172[1] : 2nd. Drive data set (DDS)
P2172[2] : 3rd. Drive data set (DDS)
Note:
This voltage controls bits 7 and 8 in status word 3 (r0053).
P2173[3]

Delay time DC-link voltage

CStat:
CUT
P-Group: ALARMS
Defines delay time prior to activation of threshold comparison.
Index:
P2173[0] : 1st. Drive data set (DDS)
P2173[1] : 2nd. Drive data set (DDS)
P2173[2] : 3rd. Drive data set (DDS)
Details:
See diagram in P2172 (threshold DC-link voltage)
216
Datatype: U16
Unit: V
Active: Immediately
QuickComm.: No
P2173
Datatype: U16
Unit: ms
Active: Immediately
QuickComm.: No
Issue 01/06
Min:
0
Def:
800
Max:
2000
t
t
P2173
t
Min:
0
Def:
10
Max:
10000
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Level
3
Level
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents