Issue 01/06
3.35

Faults, Alarms, Monitoring

P2100[3]

Alarm number selection

CStat:
CT
P-Group: ALARMS
Selects up to 3 faults or warnings for non-default reactions.
Index:
P2100[0] : Fault Number 1
P2100[1] : Fault Number 2
P2100[2] : Fault Number 3
Example:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0] = 5, then select the desired
reaction in P2101[0] (in this case, set P2101[0] = 3).
Note:
All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (e.g.
overcurrent) cannot be changed from the default reactions.
P2101[3]

Stop reaction value

CStat:
CT
P-Group: ALARMS
Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction).
This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
Possible Settings:
0
No reaction, no display
1
OFF1 stop reaction
2
OFF2 stop reaction
3
OFF3 stop reaction
4
No reaction warning only
Index:
P2101[0] : Stop reaction value 1
P2101[1] : Stop reaction value 2
P2101[2] : Stop reaction value 3
Note:
-
Settings 0 - 3 only are available for fault codes.
-
Settings 0 and 4 only are available for warnings.
-
Index 0 (P2101) refers to fault/warning in index 0 (P2100).
P2103[3]

BI: 1. Faults acknowledgement

CStat:
CT
P-Group: COMMANDS
Defines first source of fault acknowledgement, e.g. keypad/DIN, etc. (depending on setting).
Index:
P2103[0] : 1st. Command data set (CDS)
P2103[1] : 2nd. Command data set (CDS)
P2103[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Parameter Description
Level
Min:
0
3
Def:
0
Max:
65535
Level
Min:
0
3
Def:
0
Max:
4
Level
Min:
0:0
3
Def:
722:2
Max:
4000:0
207