Run Time Counter; Aop Real Time Clock - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
r2114[2]

Run time counter

P-Group: ALARMS
Displays run time counter.
It is the total time the drive has been powered up. When power goes value is saved, then restored on
powerup. The run time counter r2114 will be calculate as followed:
-
Multiply the value in r2114[0], by 65536 and then add it to the value in r2114[1].
-
The resultant answer will be in seconds.
When AOP is not connected, the time in this parameter is used by r0948 to indicate when a fault has
occured.
Index:
r2114[0] : System Time, Seconds, Upper Word
r2114[1] : System Time, Seconds, Lower Word
Example:
If r2114[0] = 1 & r2114[1] = 20864
We get 1 * 65536 + 20864 = 86400 seconds which equals 1 day.
P2115[3]

AOP real time clock

CStat:
CT
P-Group: ALARMS
Displays AOP real time.
All of the frequency inverters have an internal time generator function which is used to time-stamp and log
erroneous conditions. Therefore there is no battery-buffered real-time clock (RTC). The frequency inverters
can support a software-controlled RTC where the RTC must be set from the AOP or via an interface. When
using the AOP, this synchronization is automatic. When a serial interface is used, a task must be sent from
the higher-level control to write into the parameter. If the AOP is withdrawn during operation, or if the bus is
interrupted, then the real-time clock runs further using the runtime counter. The real-time clock is reset to
zero only after power off.
The time is stored in a word array parameter P2115. This parameter number is common to all invertes.
Inverters not supporting this feature would respond with parameter not recognised - a Master will ignore
this. The time will be set by USS Protocol standard word array parameter write telegrams.
Within the AOP, while it is acting as a USS Master, at each tick of the heartbeat, the list of available USS
Slaves will be flagged with a time update request. As the Master runs around the list of USS slaves on its
next USS update cycle, if there are no higher priority tasks to perform, and the slave still has its time update
flag set, then an array parameter write telegram will be issued, containing the current time. The request for
that slave is cancelled if the slave responds correctly. The AOP will not need to read the time from the
slave.
Time is maintained in a word array parameter and encoded as follows - the same format will be used in fault
report logs.
Index
0
1
2
Time is measured from Jan 1st 2000. Values are in binary form.
Index:
P2115[0] : Real Time, Seconds+Minutes
P2115[1] : Real Time, Hours+Days
P2115[2] : Real Time, Month+Year
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Datatype: U16
Active: Immediately
High Byte (MSB)
Low Byte (LSB)
Seconds (0 - 59)
Minutes (0 - 59)
Hours (0 - 23)
Days (1 - 31)
Month (1 - 12)
Years (00 - 250)
Parameter Description
Min:
-
Unit: -
Def:
-
Max:
-
Min:
0
Unit: -
Def:
0
QuickComm.: No
Max:
65535
Level
3
Level
3
209

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents