Parameter Description
P0706[3]

Function of digital input 6

CStat:
CT
P-Group: COMMANDS
Selects function of digital input 6.
Possible Settings:
0
Digital input disabled
1
ON/OFF1
2
ON reverse /OFF1
3
OFF2
- coast to standstill
4
OFF3
- quick ramp-down
9
Fault acknowledge
10
JOG right
11
JOG left
12
Reverse
13
MOP up (increase frequency)
14
MOP down (decrease frequency)
15
Fixed setpoint (Direct selection)
16
Fixed setpoint (Direct selection + ON)
25
DC brake enable
29
External trip
33
Disable additional freq setpoint
99
Enable BICO parameterization
Index:
P0706[0] : 1st. Command data set (CDS)
P0706[1] : 2nd. Command data set (CDS)
P0706[2] : 3rd. Command data set (CDS)
Details:
See P0701 (function of digital input 1).
P0707[3]

Function of digital input 7

CStat:
CT
P-Group: COMMANDS
Selects function of digital input 7 (via analog input).
Possible Settings:
0
Digital input disabled
1
ON/OFF1
2
ON reverse /OFF1
3
OFF2
- coast to standstill
4
OFF3
- quick ramp-down
9
Fault acknowledge
10
JOG right
11
JOG left
12
Reverse
13
MOP up (increase frequency)
14
MOP down (decrease frequency)
25
DC brake enable
29
External trip
33
Disable additional freq setpoint
99
Enable BICO parameterization
Index:
P0707[0] : 1st. Command data set (CDS)
P0707[1] : 2nd. Command data set (CDS)
P0707[2] : 3rd. Command data set (CDS)
Note:
Signals above 4 V are active, signals below 1,6 V are inactive.
Details:
See P0701 (function of digital input 1).
80
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Issue 01/06
Min:
0
Def:
15
Max:
99
Min:
0
Def:
0
Max:
99
MICROMASTER 440
Parameter List