Parameter Description
P2235[3]

BI: Enable PID-MOP (UP-cmd)

CStat:
CT
P-Group: COMMANDS
Defines source of UP command.
Index:
P2235[0] : 1st. Command data set (CDS)
P2235[1] : 2nd. Command data set (CDS)
P2235[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
19.D
= Keypad UP button
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
P2236[3]

BI: Enable PID-MOP (DOWN-cmd)

CStat:
CT
P-Group: COMMANDS
Defines source of DOWN command.
Index:
P2236[0] : 1st. Command data set (CDS)
P2236[1] : 2nd. Command data set (CDS)
P2236[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E
= Keypad DOWN button
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
P2240[3]

Setpoint of PID-MOP

CStat:
CUT
P-Group: TECH
Setpoint of the motor potentiometer.
Allows user to set a digital PID setpoint in [%].
Index:
P2240[0] : 1st. Drive data set (DDS)
P2240[1] : 2nd. Drive data set (DDS)
P2240[2] : 3rd. Drive data set (DDS)
Note:
P2240 = 100 % corresponds to 4000 hex
230
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: Float
Unit: %
Active: Immediately
QuickComm.: No
Issue 01/06
Min:
0:0
Def:
19:13
Max:
4000:0
Min:
0:0
Def:
19:14
Max:
4000:0
Min:
-200.00
Def:
10.00
Max:
200.00
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Level
3
Level
3
Level
2