Parameter Description
P2222[3]

BI: Fixed PID setp. select Bit 2

CStat:
CT
P-Group: COMMANDS
Defines command source of fixed PID setpoint selection Bit 2
Index:
P2222[0] : 1st. Command data set (CDS)
P2222[1] : 2nd. Command data set (CDS)
P2222[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
P2223[3]

BI: Fixed PID setp. select Bit 3

CStat:
CT
P-Group: COMMANDS
Defines command source of fixed PID setpoint selection Bit 3
Index:
P2223[0] : 1st. Command data set (CDS)
P2223[1] : 2nd. Command data set (CDS)
P2223[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
r2224

CO: Act. fixed PID setpoint

P-Group: TECH
Displays total output of PID fixed setpoint selection.
Note:
r2224 = 100 % corresponds to 4000 hex
P2225[3]
Fixed PID setpoint mode - Bit 4
CStat:
CT
P-Group: TECH
Direct selection or direct selection + ON Bit 4 for PID setpoint.
Possible Settings:
1
Direct selection
2
Direct selection + ON command
Index:
P2225[0] : 1st. Command data set (CDS)
P2225[1] : 2nd. Command data set (CDS)
P2225[2] : 3rd. Command data set (CDS)
P2226[3]

BI: Fixed PID setp. select Bit 4

CStat:
CT
P-Group: COMMANDS
Defines command source of fixed PID setpoint selection Bit 4
Index:
P2226[0] : 1st. Command data set (CDS)
P2226[1] : 2nd. Command data set (CDS)
P2226[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
228
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Datatype: Float
Unit: %
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Issue 01/06
Min:
0:0
Def:
0:0
Max:
4000:0
Min:
0:0
Def:
722:3
Max:
4000:0
Min:
-
Def:
-
Max:
-
Min:
1
Def:
1
Max:
2
Min:
0:0
Def:
722:4
Max:
4000:0
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Level
3
Level
3
Level
2
Level
3
Level
3