Command Source - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
3.8

Command source

P0700[3]
Selection of command source
CStat:
CT
P-Group: COMMANDS
Selects digital command source.
Possible Settings:
0
Factory default setting
1
BOP (keypad)
2
Terminal
4
USS on BOP link
5
USS on COM link
6
CB on COM link
Index:
P0700[0] : 1st. Command data set (CDS)
P0700[1] : 2nd. Command data set (CDS)
P0700[2] : 3rd. Command data set (CDS)
Example:
Changing form P0700 = 1 to P0700 = 2 sets all digital inputs to default settings.
BOP
Terminals
USS
BOP link
USS
COM link
CB
COM link
Caution:
Be aware, by changing of parameter P0700 all BI parameters are reset to the default value or modified as
listed in the table below.
If the Inverter is being controlled via the AOP, select USS (with the corresponding interface) for the
Command Source. If the AOP is connected to the BOP-Link Interface, then set Parameter P0700 to the
value 4 (P0700 = 4).
Note:
Changing this parameter sets (to default) all settings on item selected (see table).
P0700 = 0
P0701
1
P0702
12
P0703
9
P0704
15
P0705
15
P0706
15
P0707
0
P0708
0
P0731
52.3
P0732
52.7
P0733
0.0
P0800
0.0
P0801
0.0
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Active: first confirm
P0700 = 2
Sequence control
Setpoint
channel
P0700 = 1
P0700 = 2
0
1
0
12
9
9
15
15
15
15
15
15
0
0
0
0
52.3
52.3
52.7
52.7
0.0
0.0
0.0
0.0
0.0
0.0
Parameter Description
Min:
Unit: -
Def:
QuickComm.: Yes
Max:
Motor
control
P0700 = 4
P0700 = 5
P0700 = 6
0
0
0
0
0
0
9
9
9
15
15
15
15
15
15
15
15
15
0
0
0
0
0
0
52.3
52.3
52.3
52.7
52.7
52.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Level
0
1
2
6
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents