Parameter Description
P0819[3]

Copy drive data set (DDS)

CStat:
CT
P-Group: COMMANDS
Calls "Copy Drive Data Set (DDS)" function.
The list of all Drive Data Sets (DDS) are shown in the opening instructions of the Parameter List (PLI).
Index:
P0819[0] : Copy from DDS
P0819[1] : Copy to DDS
P0819[2] : Start copy
Example:
Copying of all values from DDS1 to DDS3 can be accomplished by the following procedure:
P0819[0] = 0
P0819[1] = 2
P0819[2] = 1
Note:
Start value in index 2 is automatically reset to "0" after execution of function.
P0820

BI: DDS bit 0

CStat:
CT
P-Group: COMMANDS
Selects command source from which to read Bit 0 for selecting a drive data set (DDS).
Drive running
Drive ready
Selecting DDS
BI: DDS bit 1
P0821
(0:0)
BI: DDS bit 0
P0820
(0:0)
DDS active
r0051[1]
100
Datatype: U16
Active: first confirm
1. DDS
3. DDS
Start copy
P0005
P0291
P0300
P0304
P0305
. .
. .
.
P2484
P2487
P2488
1. DDS
Datatype: U32
Active: first confirm
3
2
1
0
Changeover time
approx. 50 ms
3
2
1
0
Min:
Unit: -
Def:
QuickComm.: No
Max:
[0]
[1]
[2]
. .
. .
. .
. .
. .
. .
.
.
.
2. DDS 3. DDS
Min:
Unit: -
Def:
QuickComm.: No
Max:
Changeover time
approx. 50 ms
MICROMASTER 440
Issue 01/06
Level
0
2
0
2
Level
0:0
3
0:0
4095:0
t
CO/BO: Act CtrlWd2
r0055
.05
r0055
.05
CO/BO: Act CtrlWd2
r0055
.04
r0055
.04
t
CO: Active DDS
r0051 [2]
.01
t
Parameter List
6SE6400-5BB00-0BP0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents