Control Terminals On Opta1 - Danfoss Vacon NXP Series Operating Manual

Air-cooled wall-mounted and standalone
Hide thumbs Also See for Vacon NXP Series:
Table of Contents

Advertisement

Operating guide | VACON® NXS/NXP Air-cooled

7.3.2 Control Terminals on OPTA1

The figure shows the basic description of the terminals of the I/O board. For more information, see
OPTA1 Basic
Board. For more information on control terminals, see VACON
Reference potentiometer,
1-10kΩ
*) See figure in
7.3.2.2 Jumper Selections on the OPTA1 Basic Board
Illustration 31:
Control Terminal Signals on OPTA1
Parameter references for I/O on control panel and NCDrive are: An.IN:A.1, An.IN:A.2, DigIN:A.1, DigIN:A.2, DigIN:A.3, DigIN:A.4, DigIN:A.5,
DigIN:A.6, AnOUT:A.1 and DigOUT:A.1.
To use the control voltage output +24 V/EXT+24 V:
wire the +24 V control voltage to digital inputs through an external switch. OR
use the control voltage to power up external equipment, such as encoders and auxiliary relays.
The specified total load on all available +24 V/EXT+24 V output terminals must not exceed 250 mA.
78 | Danfoss A/S © 2018.06
Terminal
+10V
Reference voltage
1
ref
Analogue input,
AI1+
2
voltage or current
GND/AI1-
Analogue input common
3
Analogue input,
AI2+
4
voltage or current
GND/AI2-
Analogue input common
5
24 V aux. voltage
+24V
6
GND
I/O ground
7
DIN1
Digital input 1
8
DIN2
Digital input 2
9
DIN3
Digital input 3
10
CMA
Common A for DIN1—DIN3
11
+24V
Control voltage output
12
GND
I/O ground
13
Digital input 4
DIN4
14
DIN5
Digital input 5
15
DIN6
Digital input 6
16
CMB
Common B for DIN4-DIN6
17
AO1+
18
Analogue signal (+output)
AO1-
19
Analogue output common
DO1
Open collector output
20
®
All in One Application manual.
Standard I/O board
Signal
Description
Maximum current 10 mA
Selection V/mA with jumper block X1 (*)
0...+10 V (Ri = 200 kΩ)
(-10V...+10V Joystick ctrl, sel. with jumper)
0-20 mA (Ri =250 Ω)
Differential input if not connected to ground
Allows ±20 V common mode voltage to GND
Selection V/mA with jumper block X1 (*)
0...+10 V (Ri = 200 kΩ)
(-10V...+10V Joystick ctrl, sel. with jumper)
0-20 mA (Ri =250 Ω)
Differential input if not connected to ground
Allows ±20 V common mode voltage to GND
±15%, max. 250 mA (all boards total)
150 mA (from single board)
Can also be used as external power back-up for
the control unit (and fieldbus)
Ground for reference and controls
Ri = min. 5 kΩ
18-30 V = 1
Digital inputs can be disconnected from ground (*)
Same as terminal #6
Same as terminal #7
Ri = min. 5 kΩ
18-30 V = 1
Must be connected to GND or 24 V of I/O term.
or to ext.24 V or GND
Selection with jumper block X3 (*)
Output signal range: Current 0(4)-20 mA,
RL max 500 Ω or
Voltage 0-10 V, RL >1kΩ
Selection with jumper block X6 (*)
Maximum Uin = 48 VDC
Maximum current = 50 mA
Control Unit
7.3.2.2 Jumper Selections on the
DPD00910G