Wiring To Control Terminals; Enabling Motor Operation (Terminal 27); Voltage/Current Input Selection (Switches) - Danfoss VLT AutomationDrive FC 302 Instruction Manual

0–315 kw d-frame
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Electrical Installation
Terminal description
Default
Terminal
Parameter
setting
Serial communication
61
-
68 (+)
8-3*
69 (-)
8-3*
Relays
[0] No
01, 02, 03
5-40 [0]
operation
04, 05, 06
5-40 [1]
[0] No
operation
Table 4.2 Terminal Description Serial Communication
Additional terminals:
two form C relay outputs. The location of the
outputs depends on the adjustable frequency
drive configuration.
Terminals located on built-in optional equipment.
See the manual provided with the equipment
option.

4.8.2 Wiring to Control Terminals

Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in Figure 4.25.
12 13 18 19 27 29 32 33
Figure 4.25 Connecting Control Wires
NOTICE!
Keep control wires as short as possible and separate
from high power cables to minimize interference.
MG34U422
Instruction Manual
Description
Integrated RC filter for
cable shield. ONLY for
connecting the shield
in the event of EMC
problems.
RS485 interface. A
control card switch is
See chapter 8.5 Cable Specifications for control terminal
provided for
wiring sizes and chapter 6 Application Set-up Examples for
termination resistance.
typical control wiring connections.
Form C relay output.
4.8.3 Enabling Motor Operation (Terminal
For AC or DC voltage
and resistive or
inductive loads.
A jumper wire may be required between terminal 12 (or
13) and terminal 27 for the adjustable frequency drive to
operate when using factory default programming values.
NOTICE!
The adjustable frequency drive cannot operate without a
signal on terminal 27, unless terminal 27 is re-
programmed.
4.8.4 Voltage/Current Input Selection
The analog input terminals 53 and 54 allow setting of
input signal to voltage (0–10 V) or current (0/4–20 mA).
Default parameter setting:
Danfoss A/S © 06/2015 All rights reserved.
1.
Open the contact by inserting a small screwdriver
into the slot above the contact and push the
screwdriver slightly upwards.
2.
Insert the bare control wire into the contact.
3.
Remove the screwdriver to fasten the control wire
into the contact.
4.
Ensure that the contact is firmly established and
not loose. Loose control wiring can be the source
of equipment faults or reduced performance.
27)
Digital input terminal 27 is designed to receive 24
V DC external interlock command.
When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or
13 to terminal 27. This provides an internal 24 V
signal on terminal 27.
When the status line at the bottom of the LCP
reads AUTO REMOTE COAST, this indicates that the
unit is ready to operate but is missing an input
signal on terminal 27.
When factory installed optional equipment is
wired to terminal 27, do not remove that wiring.
(Switches)
Terminal 53: Speed reference signal in open-loop
(see parameter 16-61 Terminal 53 Switch Setting).
Terminal 54: Feedback signal in closed-loop (see
parameter 16-63 Terminal 54 Switch Setting).
4
4
33

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AutomationDrive FC 302 and is the answer not in the manual?

Questions and answers

Table of Contents