Disabling The Stop Motor Function; Special Functions In Keypad Control Menu - Danfoss Vacon NXP Series Operating Manual

Air-cooled wall-mounted and standalone
Hide thumbs Also See for Vacon NXP Series:
Table of Contents

Advertisement

Operating guide | VACON® NXS/NXP Air-cooled
Procedure
1. In the Keypad control menu (M3), find the Keypad direction with the Menu buttons Up and Down.
2. To go to the edit mode, push the Menu button Right.
3. Select the direction with Menu buttons Up and Down.
The rotation direction changes on the control panel.
4. To make the motor to agree with the set rotation direction, select the keypad as the control mode, see
Mode.

8.4.6 Disabling the Stop Motor Function

Context:
As a default, the motor stops when the Stop button is pushed no matter what is the control mode. Use these instructions to disable
this function.
Procedure
1. In the Keypad control menu (M3), find the page 3.4. Stop button with the Browser buttons.
2. To go to the edit mode, push the Menu button Right.
3. To select Yes or No, use the Browser buttons.
4. Accept the selection with the [enter] button.
When the Stop motor function is not active, the Stop button stops the motor only when the keypad is the control mode.

8.4.7 Special Functions in Keypad Control Menu

8.4.7.1 Selecting the Keypad as the Control Mode
Context:
This is a special function only available in menu M3.
Prerequisites:
Make sure to be in the menu M3 and control mode is other than keypad.
Procedure
1. Do one of the following options:
Keep the Start button pushed down for 3 s when the motor is in RUN state.
Keep the Stop button pushed down for 3 s when the motor is stopped.
In other menu than M3, when the keypad is not the active control mode and the start button is pushed, an error message Keypad
Control NOT ACTIVE shows. In some applications this error message is not shown.
The keypad is selected as the control mode and the current frequency reference and direction is copied to the control
panel.