1. Strip the motor cable, the mains cable, and the brake resistor cable. See
2. To move the cables through grommets, cut the them open.
Do not cut the grommet openings wider than what is necessary for the used cables.
If the grommets fold in when putting the cable, pull the cable back to make the grommets straight.
Use a grommet as an alternative to the grommet in types where this is necessary.
3. Attach the grommet and the cable until the frame of the drive goes into the groove of the grommet.
With the protection rating IP54 (UL Type 12), the connection between the grommet and the cable must be tight. Pull the first
bit of the cable out of the grommet until it stays straight.
If this is not possible, make the connection tight with some insulation tape or a cable tie.
4. Connect the cables. See the correct tightening torques in
Connect the phase conductors of the mains cable and of the motor cable into the correct terminals. If a brake resistor cable is
used, connect its conductors into the correct terminals.
Attach the grounding conductor of each cable to a grounding terminal with a grounding clamp for grounding conductor.
5. Expose the shield of all cables to make a 360° connection with the grounding clamp for cable shield.
Danfoss A/S © 2018.06
12.4 Cable Stripping Lengths
12.6 Tightening Torques of the
Electrical Installation
Terminals.