Operating guide | VACON® NXS/NXP Air-cooled
Procedure
1. Remove the external Start signal before resetting the fault to prevent that the drive starts again without a note.
2. There are 2 options to reset a fault:
- Push the [reset] button on the control panel for 2 s.
- Use a reset signal from the I/O terminal or fieldbus.
The display goes back to the same state it was before the fault.

11.3 Creating Service Info File

Context:
Use these instructions to create a service info file in VACON
Prerequisites:
®
Make sure the VACON
NCDrive PC tool is installed on the computer. To install it, go to our website
downloads/portal/
.
Procedure
®
1. Open the VACON
NCDrive.
2. Go to File and select Service Info....
The service information file opens.
3. Save the service info file on the computer.
124 | Danfoss A/S © 2018.06
®
NCDrive PC tool to help to troubleshoot in a fault situation.
Fault Tracing
http://drives.danfoss.com/
DPD00910G