Cable And Fuse Sizes For 208-240 V And 380-500 V, Fr4 To Fr9, North America - Danfoss Vacon NXP Series Operating Manual

Air-cooled wall-mounted and standalone
Hide thumbs Also See for Vacon NXP Series:
Table of Contents

Advertisement

Operating guide | VACON® NXS/NXP Air-cooled
Enclosure
Drive type
size
FR7
0075 2
0072 5
0088 2
0087 5
0114 2
0105 5
FR8
0140 2
0140 5
0170 2
0168 5
0205 2
0205 5
FR9
0261 2
0261 5
0300 2
0300 5
1
Uses a correction factor 0.7
12.3.3 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9, North America
Table 35: Cable and Fuse Sizes for VACON
Enclo-
Drive type
sure size
FR4
0003 2—0008 2
0003 5—0007 5
0009 5
0011 2—0012 2
0012 5
138 | Danfoss A/S © 2018.06
I
[A]
Fuse
Mains, motor and
L
(gG/gL) [A]
brake resistor cable Cu
(1)
75
80
3*25+16
72
88
100
3*35+16
87
114
125
3*50+25
105
140
160
3*70+35
168
200
3*95+50
205
250
3*150+70
261
315
3*185+95 or
2*(3*120+70)
300
315
2*(3*120+70)
®
NXS/NXP, North America
Fuse Class
Mains, Motor, and brake re-
Fast Act-
sistor cable Cu [AWG]
ing (T/J)
[A]
10
3*16 AWG + 16 AWG
15
3*16 AWG + 16 AWG
15
3*14 AWG + 14 AWG
Mains terminal [mm
2
[mm
]
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
25–95 Cu/Al
95–185 Cu/Al
95–185 Cu/Al
95–185 Cu/Al
95–185 Cu/Al
Mains terminal [AWG]
(1) (2)
18 AWG - 4 AWG
18 AWG - 4 AWG
18 AWG - 4 AWG
Specifications
Grounding terminal
2
]
2
[mm
]
6–70
6–70
6–70
6–95
6–95
6–95
6–95
6–95
Grounding terminal
[AWG]
18 AWG - 4 AWG
18 AWG - 4 AWG
18 AWG - 4 AWG
DPD00910G

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vacon nxs series

Table of Contents