Operating guide | VACON® NXS/NXP Air-cooled
Drive type
0075 2-0114 2
0072 5-0105 5
0041 6-0052 6
0140 2-0205 2
0140 5-0205 5
0062 6-0100 6
0261 2-0300 2
0261 5-0300 5
0125 6-0208 6
To change the fan with the motor cables connected, the necessary clearance on the 2 sides of the drive is 150 mm (5.91 inch).
The minimum clearance to change the fan.
Table 7: Necessary Quantity of Cooling Air
Drive type
The quantity of cooling air [m
0003 2-0012 2
70
0003 5-0012 5
0017 2-0031 2
190
0016 5-0031 5
0048 2-0061 2
425
0038 5-0061 5
0004 6-0034 6
0075 2-0114 2
425
0072 5-0105 5
0041 6-0052 6
0140 2-0205 2
650
0140 5-0205 5
0062 6-0100 6
0261 2-0300 2
1000
0261 5-0300 5
0125 6-0208 6
Danfoss A/S © 2018.06
A
B
80
80
(3.15)
(3.15)
80
80
(3.15)
(3.15)
()
50
80
(1.97)
(3.15)
3
/h]
C
300
(11.81)
300
(11.81)
400
(15.75)
The quantity of cooling air [CFM]
41.2
112
250
250
383
589
Mounting the Unit
D
100
(3.94)
300
(11.81)
250 / 350
(9.84) / (13.78)
()
DPD00910G | 35