Trip 9 Time/Braking Resistor Resistance; Remote Keypad Battery Low/Auto-Tune Active; Limit Switch Active; Hold Drive Healthy On Under Voltage - Emerson Unidrive M200 Parameter Reference Manual

Open-loop mode
Hide thumbs Also See for Unidrive M200:
Table of Contents

Advertisement

Parameter
10.060 Trip 9 Time
Short description
Shows the time at which trip 9 occurred
Mode
Open‑loop
0
Minimum
(Display: 00:00:00)
Default
Type
32 Bit Power Down Save
Display Format
Time
Coding
RO, ND, NC, PT
See Trip 0 (10.020).
Parameter
10.061 Braking Resistor Resistance
Short description
Set to the resistance value of the braking resistor
Mode
Open‑loop
Minimum
0.00
Default
0.00
Type
32 Bit User Save
Display Format
Standard
Coding
RW
See Braking Resistor Rated Power (10.030).
Parameter
10.064 Remote Keypad Battery Low
Short description
Indicates that the real time clock battery in the remote keypad is low
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Remote Keypad Battery Low (10.064) is set to one when a keypad is connected to the drive user comms port with an internal real-time clock and the battery is not
fitted or the voltage is below the minimum threshold.
Parameter
10.065 Auto-tune Active
Short description
Indicates that an auto-tune sequence is active
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Auto-tune Active (10.065) is set to one while an auto-tune sequence is active.
Parameter

10.066 Limit switch active

Short description
Indicates that a limit switch is enabled and active
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Limit switch active (10.066) is set to one when a limit switch is enabled and active.
Parameter

10.068 Hold Drive Healthy on Under Voltage

Short description
Set to hold drive healthy if the drive is in the under voltage state
Mode
Open‑loop
Minimum
0
Default
0
Type
1 Bit User Save
Display Format
Standard
Coding
RW
Hold Drive Healthy on Under Voltage (10.068) can be used to hold the drive healthy active (Drive Healthy (10.001) = 1 and not flash the status LED on the front of
the drive) when the drive is in the under voltage state (Under Voltage Active (10.016) = 1).
If Hold Drive Healthy on Under Voltage (10.068) = 0 and Under Voltage Active (10.016) = 1, then Drive Healthy (10.001) will be set to 0 and the status LED on the
front of the drive will flash.
If Hold Drive Healthy on Under Voltage (10.068) = 1, Under Voltage Active (10.016) = 1 and the drive is not tripped (i.e. Drive Status (10.101) does not equal 9), then
Drive Healthy (10.001) will be set to 1 and the status LED on the front of the drive will not flash.
If the drive is tripped then Drive Healthy (10.001) will be set to 0 and the status LED will flash independent of what Hold Drive Healthy on Under Voltage (10.068) is
set to.
164
235959
Maximum
(Display: 23:59:59)
Units
Update Rate
Write on trip
Decimal Places
0
Maximum
10000.00
Units
Update Rate
Background read
Decimal Places
2
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents