Differential for anti-freezing control: (-12.0 to 12.0°C; -21.0 to 21.0°F) the regulation stops if
SAF
T<SET+SAF
Alarm relay deactivation: (n; Y) n = no, it is not possible to deactivate neither the buzzer nor any
tbA
digital output set as an alarm; Y = yes, it is possible to deactivate both the buzzer and the digital
output set as an alarm.

5.1.8 Digital and analogue output configuration parameters - out

Relay output oAx configuration: (nu; CP1; dEF; FAn; ALr; LiG; AUS; db; onF; HES; Cnd)
nu=not used; CP1=compressor; dEF=defrost; FAn=ventilators; ALr=alarm; LiG=light;
oAx
AUS=auxiliary relay; onF=always ON with instrument ON; db=neutral zone; HES=night
(x=2, 3, 4)
blinds; Cnd=condenser fan; CP2=second compressor; dF2=second defrost; HEt=heater
control; inV=do not use it.
Alarm relay polarity: (oP; CL) oP = alarm activated by closing the contact; CL = alarm
AoP
activated by opening the contact

5.1.9 Digital input configuration parameters - inP

Base time for digital inputs: (SEC; Min) SEC = seconds; Min = minutes. Delay in activating the
ibt
function linked to the digital inputs.
Digital input 1 polarity: (oP; CL) oP = activated by closing the contact; CL = activated by opening
i1P
the contact.
Digital input 1 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; CC;
EMt)
nu=not used
dor = door switch function
dEF = defrost activation
AUS = auxiliary output
ES = energy saving mode activation
EAL = external warning alarm
i1F
bAL = external lock alarm
PAL = external pressure alarm
FAn = evaporator fan control
HdF = holiday defrost
onF = ON/OFF status change
LiG = light output control
CC = change configuration (between C1 and C2)
EMt = Motion sensor X-MOD
Digital inputs 1 alarm delay (base time depends on par. ibt): (0 to 255) delay between the
did
detection of an external event and the activation of the relative function.
Digital input 2 polarity: (oP; CL) oP = activated by closing the contact; CL = activated by opening
i2P
the contact.
Digital input 2 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; CC;
EMt)
nu = not used
dor = door switch function
dEF = defrost activation
AUS = auxiliary output
ES = energy saving mode activation
EAL = external warning alarm
i2F
bAL = external lock alarm
PAL = external pressure alarm
FAn = evaporator fan control
HdF = holiday defrost
onF = ON/OFF status change
LiG = light output control
CC = change configuration (between C1 and C2)
EMt = Motion sensor X-MOD
Digital inputs 2 alarm delay (base time depends on par. ibt): (0 to 255) delay between the
d2d
detection of an external event and the activation of the relative function.
Number of external pressure switch alarms before stopping the regulation: (0 to 15) after
nPS
reaching nPS events in the digital input alarm delay (par. dxd), the regulation will be stopped and a
manual restart (ON/OFF, power OFF and power ON) will be required