Analog Input Option; Overview - Emerson AXIMA 2000 Installation Manual

Table of Contents

Advertisement

AXIMA 2000/4000 In-

Analog Input Option

Overview

An Analog Input feature is available as a factory option only. It
allows the AXIMA 2000/4000 to accept single-ended and differential
inputs. You can configure these inputs with up to eight single-ended
inputs, four differential inputs or combinations of single and
differential inputs.
NOTE:
The source of each analog input can be selected to be either from the
analog input connector on the left side of the unit or the axis
connector on the front of the unit. This is done by setting a DIP switch
located behind the left side panel, of the AXIMA 2000/4000
controller. This selection is provided to allow easy interface to the
analog signal from an E Series drive.
Figure 40 Analog DIP Switch Location Behind the Left-Side Panel
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
If you wish to add the Analog Input option to an existing
AXIMA 2000/4000 controller, it must be returned to the
factory.
1
2
3
4
1
2
3
4
of the AXIMA 2000/4000
P/N 400290-00
NOTE: DIP SWITCHES ARE MOUNTED
BEHIND THE LEFT PANEL OF THE AXIMA
CONTROLLER
1
2
3
4
1
2
3
4
AXIS INPUTS (DEFAULT)
EXTERNAL INPUTS
51