Single Phase Circuit Breaker Close Failure Protection 50Bfc; Identification; Function Block; Functionality - ABB RER620 Technical Manual

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

Section 4
Protection functions
4.5.2
4.5.2.1
4.5.2.2
4.5.2.3
4.5.2.4
244

Single Phase Circuit breaker close failure protection 50BFC

Identification

Function description
Circuit breaker close failure protection

Function block

50BFC
CLS_RET_A
CLS_RET_B
START
CLS_RET_C
START_ A
START_ B
START_ C
BLOCK
POSCLOSE _A
_B
POSCLOSE
POSCLOSE
_C
CB_ FAULT
Figure 113:
Function block

Functionality

The breaker close failure function 50BFC is activated by close commands from either
internal auto reclose commands or external commands through START inputs. The pickup
or start input command can be single phase or common for all three phases depending on
the choice whether single phase or three phase breaker operation mode is chosen. 50BFC
includes a single or all three phase unconditional re-close function.
The function has a timer for attempting automatically a re-close timer for the repeated
closing of the intended breaker. A minimum close pulse length can be set independently
for the output.
The function contains a blocking functionality. It is possible to block the function outputs,
if desired.

Operation principle

The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are Enable and Disable.
The operation of breaker close failure protection can be described by using a module
diagram, as shown in the top portion of the logic diagram shown in the figure next page.
The signal inputs POS_CLOSE_A, START_A and BLOCK inputs are processed in the
Start logic block. Any attempt to close the A pole of the breaker, as decided by the input
START_A input going high generates command to try reclosing the breaker after the set
close delay time, for a duration of close pule time, set in the unit. Alarm generation on
unsuccessful attempt can be done external to this logic in the unit.
IEC 61850
identification
SCCBRBCF
CLSRET
1MAC309294-MB F
IEC 60617
ANSI/IEEE C37.2
identification
device number
SCCBRBCF
50BFC
Technical Manual
RER620