6.
Install conduit between the UPS and RMP II. See Figure 5-12 for RMP II knockout hole location.
7 .
Install wiring between the UPS and RMP II. See Figure 5-2 and Table 5-1 for the Hot Sync CAN Bridge
Card terminal location and wiring information, and Figure 5-7, Figure 5-8, and Table 5-5 for the RMP II
terminal location and wiring information.
NOTE
120 Vac for the RMP II should be supplied from the critical bus by facility planners or
the customer.
8.
Install 120 Vac power wiring from the critical bus to the RMP II. See Figure 5-7, Figure 5-8, and Table 5-5
for the terminal location and wiring information.
9.
Close the front door and secure the latch.
10. Restart the UPS. See Chapter 7, "UPS Operating Instructions" for startup instructions
Terminal TB1
Signal Connections
from the UPS

Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations

®
®
Eaton
Power Xpert
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual
Installing Options and Accessories
Ground
Terminal
P-164000563—Rev 04 www.eaton.com/powerquality
Terminal TB3
120 Vac Power
5-9