INSTALLING OPTIONS AND ACCESSORIES
UPS Can Card J3
Twisted Pair
Figure 5‐8. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring
5-10
Eaton Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
Terminal TB1
Signal Connections
from the UPS
Figure 5‐7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations
RMP II, RIM II, or SCM II
Table 5‐5. RMP II, RIM II, or SCM II Wiring Terminations
From
UPS CAN Card
J3–6 (TX)
J3–7 (TX)
N/A
N/A
N/A
To
Tightening Torque
RMP II, RIM II, or SCM II
TB1–5 (RDX*)
TB1–4 (RDX)
TB3 Line
TB3 Neutral
Ground Terminal
2.7 (24) Maximum
S
P-164000710 Rev 1
Ground
Terminal
Terminal TB3
120 Vac Power
Ground Terminal
Neutral
120 Vac from
Critical Bus
Line
(Customer
Supplied)
Remarks
Nm (lb in)
0.9 (8)
Use twisted pair
0.9 (8)
0.9 (8)
0.9 (8)
www.eaton.com/powerquality