Chapter 9
Product Specifications
9.1 Model Numbers
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
93E-15UI-N-64×9Ah-MBS
93E-15UI-N-0-MBS
93E-15U-N-MBS
93E-15UT-N-MBS
93E-20I-N-64×9Ah-MBS
93E-20I-N-0-MBS
93E-20-N-MBS
93E-20T-N-MBS
93E-30I-N-96×9Ah-MBS
93E-30I-N-0-MBS
93E-30-N-MBS
93E-30T-N-MBS
93E-40I-N-128×9Ah-MBS
93E-40I-N-0-MBS
93E-40-N-MBS
93E-40T-N-MBS
93E-60-N-MBS
93E-60T-N-MBS
93E-80-N-MBS
93E-80T-N-MBS
9.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
9.2.1 UPS Environmental
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and storage)
Acoustical Noise
EMC
Models
Power Rating
UPS: 0 to 40°C (32 to 104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Battery: 5—25°C
Maximum 1000m (3300 ft) at 30°C without derating
-15 to +55°C, excluding batteries (prolonged storage above 40°C causes
rapid battery self-discharge)
5% to 95% maximum noncondensing
≦
≦
≦
at a 1m distance, per ISO 7779
Meets IEC 62040-2 2005 C3
Frequency
15 kVA
50/60 Hz
15 kVA
50/60 Hz
15 kVA
50/60 Hz
15 kVA
50/60 Hz
20 kVA
50/60 Hz
20 kVA
50/60 Hz
20 kVA
50/60 Hz
20 kVA
50/60 Hz
30 kVA
50/60 Hz
30 kVA
50/60 Hz
30 kVA
50/60 Hz
30 kVA
50/60 Hz
40 kVA
50/60 Hz
40 kVA
50/60 Hz
40 kVA
50/60 Hz
40 kVA
50/60 Hz
60 kVA
50/60 Hz
60 kVA
50/60 Hz
80 kVA
50/60 Hz
80 kVA
50/60 Hz
55 dB (15-20 kVA)
62 dB (30-40 kVA)
65 dB (60-80 kVA)
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
description
N- Normal type with single feed
I- Internal battery can be selected
0-without battery for internal battery type
T-Transformer UPS
MBS-with internal MBS
U-upgradable
9-1